Comp No 5116280 - Iss 2 - 11/05

 

Installation & Servicing Instructions

Baxi Platinum Combi HE Range

Gas Fired Wall Mounted Condensing Combination Boiler

Please leave these instructions with the user

page 1


Natural Gas

Baxi Platinum Combi 24 HE
G.C.No 47 075 20
Baxi Platinum Combi 28 HE
G.C.No 47 075 21
Baxi Platinum Combi 33 HE
G.C.No 47 075 22

Building Regulations and the Benchmark Commissioning Checklist

Building Regulations (England & Wales) require notification of the installation of a heating appliance to the relevant Local Authority Building Control Department. From 1 April 2005 this can be achieved via a Competent Persons Self Certification Scheme as an option to notifying the Local Authority directly. Similar arrangements will follow for Scotland and will apply in Northern Ireland from 1 January 2006.

CORGI operate a Self Certification Scheme for gas heating appliances.

These arrangements represent a change from the situation whereby compliance with Building Regulations was accepted as being demonstrated by completion of the Benchmark Logbook (which was then left on site with the customer).

With the introduction of Self Certification Schemes, the Benchmark Logbook is being withdrawn. However, a similar document in the form of a commissioning checklist and service interval record is incorporated at the back of these instructions.

Baxi is a member of the Benchmark initiative and fully supports the aims of the programme. Its aim is to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.

Building Regulations require that installations should comply with manufacturer's instructions. It is therefore important that the commissioning checklist is completed by the installer. The relevant section of Building Regulations only relates to dwellings. Therefore the checklist only applies if the appliance is being installed in a dwelling or some related structure.

The flowchart on the next page gives guidance for installers on the process necessary to ensure compliance with Building Regulations.

The boiler meets the requirements of Statutory InstrumentThe Boiler (Efficiency) Regulations 1993 No 3083and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-

Type test for purpose of Regulation 5 certified by:
Notified Body 0085.

Product/Production certified by:
Notified Body 0085.

For GB/IE only.

 

Baxi is a BS-EN ISO 9001 Accredited Company

page 2


Installer Notification Guidelines

page 3


IMPORTANT - Installation, Commissioning, Service & Repair

This appliance must be installed in accordance with the manufacturers instructions and the regulations in force. Read the instructions fully before installing or using the appliance.

In GB, this must be carried out by a competent person as stated in the Gas Safety (Installation & Use) Regulations.

Definition of competence: A person who works for a CORGI registered company and holding current certificates in the relevant ACS modules, is deemed competent.

In IE, this must be carried out by a competent person as stated in I.S. 813Domestic Gas Installations”.

Lifting - This product should be lifted and handled by two people. Stooping should be avoided and protective equipment worn where necessary. Carrying & lifting equipment should be used as required, e.g. when installing in a loft space.

The addition of anything that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty. In GB this could also infringe the Gas Safety (Installation and Use) Regulations.

Warning - Check the information on the data plate is compatible with local supply conditions.

All CORGI registered installers carry a CORGI identification card and have a registration number. You can check your installer is registered by telephoning 0870 4012300 or writing to:-

1 Elmwood
Chineham Business Park
Crockford Lane
Basingstoke
RG24 8WG

or check online at www.corgi-gas-safety.com

Legislation

Baxi declare that no substances harmful to health are contained in the appliance or used during appliance manufacture.

The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force, and only used in a suitably ventilated location.

In GB, the installation must be carried out by a CORGI Registered Installer. It must be carried out in accordance with the relevant requirements of the:

Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.

In IE, the installation must be carried out by a competent Person and installed in accordance with the current edition of I.S. 813Domestic Gas Installations’, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.

All systems must be thoroughly flushed and treated with inhibitor (see section 6.2).

Codes of Practice - refer to the most recent version

In GB the following Codes of Practice apply:

 
Standard Scope
BS 6891 Gas Installation.
BS 5546 Installation of hot water supplies for domestic purposes.
BS 5449 Forced circulation hot water systems.
BS 6798 Installation of gas fired hot water boilers.
BS 5440 Part 1 Flues.
BS 5440 Part 2 Ventilation.
BS 7074 Expansion vessels and ancillary equipment for sealed water systems.
BS 7593 Treatment of water in domestic hot water central heating systems.

In IE the following Codes of Practice apply:

 
Standard Scope
I.S. 813 Domestic Gas Installations.
The following standards give valuable additional information;
BS 5546 Installation of hot water supplies for domestic purposes.
BS 5449 Forced circulation hot water systems.
BS 7074 Expansion vessels and ancillary equipment for sealed water systems.
BS 7593 Treatment of water in domestic hot water central heating systems.

page 4


CONTENTS

1.0    Introduction
2.0    General Layout

3.0    Appliance Operation

4.0    Technical Data

5.0    Dimensions and Fixings

6.0    System Details

7.0    Site Requirements

8.0    Installation

9.0    Commissioning

10.0  Completion

11.0  Servicing

12.0  Changing Components

13.0  Combustion Check

14.0  Electrical

15.0  Short Parts List

16.0  Fault Finding

17.0  Notes

Benchmark Checklist

page 5


1.0 Introduction

1.1 Description

  1. The Baxi Platinum Combi HE is a fully automatic gas fired wall mounted condensing combination boiler. It is room sealed and fan assisted, and will serve central heating and mains fed domestic hot water.
  2. The boiler is set to give a maximum output of :-
    24 models - 24 kW DHW
                       25.9 kW CH (Condensing)
    28 models - 28 kW DHW
                       25.9 kW CH (Condensing)
    33 models - 33 kW DHW
                       30.3 kW CH (Condensing)
  3. It is designed for use on Natural Gas (G20).
  4. The boiler is suitable for use only on fully pumped sealed heating systems. Priority is given to domestic hot water.
  5. The boiler is supplied with a filling loop and integral timer.
  6. The boiler data badge gives details of the model, serial number and Gas Council number and is situated on the inner door panel. It is visible when the case front panel is removed (Fig. 1).
  7. The boiler model name and serial number are also shown on the information label on the inner face of the right hand case panel. This is for user reference.
  8. The boiler is intended to be installed in residential / commercial / light industrial E.M.C. environments on a governed meter supply only.
  9. The boiler must be installed with one of the purpose designed flues such as the standard horizontal flue kit, part no. 5111073.
  10. All systems must be thoroughly flushed and treated with inhibitor (see section 6.2).

1.2 Optional Extras

Various flue extensions, bends, vertical flue kits, control accessories etc. are available as optional extras. These are detailed in a separate publication.

NOTE: All illustrations show the Platinum Combi 24 HE unless otherwise stated.

page 6


2.0 General Layout

2.1 Layout

 
1. Expansion Vessel 15. Primary Heat Exchanger
2. Automatic Air Vent 16. Fan Assembly
3. DHW Plate Heat Exchanger 17. On/Off/Reset Selector Switch
4. Circulation Pump 18. Central Heating Temperature Control
5. Drain Off Point 19. Hot Water Temperature Control
6. Pressure Relief Valve 20. Venturi
7. Integral Timer Position 21. Air/Gas Collector
8. Central Heating System Pressure Gauge 22. Combustion Box Cover & Burner
9. PCB 23. Igniter
10. Control Box 24. Burner On Light
11. 3-Way Valve Assembly 25. Central Heating Mode Light
12. Condensate Trap 26. Domestic Hot Water Mode Light
13. Flame Sensing Electrode 27. Display
14. Spark Electrode

page 7


3.0 Appliance Operation

3.1 Central Heating Mode (Fig. 2)

  1. With a demand for heating, the pump circulates water through the primary circuit.
  2. Once main burner ignites the fan speed controls the gas rate to maintain the heating temperature measured by the temperature sensor.
  3. When the flow temperature exceeds the setting temperature, a 3 minute delay occurs before the burner relights automatically (anti-cycling). The pump continues to run during this period.
  4. When the demand is satisfied the burner is extinguished and the pump continues to run for a period of 3 minutes (Pump Overrun).

Key
1 Primary Heat Exchanger 14  Gas Inlet
2 Burner 15 Domestic Hot Water Outlet
3 Ignition Electrode 16 Heating Flow
4 Flame Sensing Electrode 17 Pressure Gauge
5 Gas Valve 18 Water Pressure Sensor
6 Pump 19 Automatic By-Pass
7 Automatic Air Vent 20 Fan
8 Plate Heat Exchanger 21 Diverter Valve Assembly
9 Flow Sensor with Filter & Regulator 22 Diverter Valve Motor
10 Pressure Relief Valve 23 Domestic Hot Water Flow Temperature Sensor
11 Boiler Drain Point 24 Safety Thermostat
12 Heating Return 25 Central Heating Temperature Sensor
13 Cold Water Inlet On/Off Valve and Filter 26 Expansion Vessel

3.2 Domestic Hot Water Mode (Fig. 3)

  1. Priority is given to the domestic hot water supply. A demand at a tap or shower will override any central heating requirement.
  2. The flow of water will operate the Hall Effect Sensor which requests the 3 way valve to change position. This will allow the pump to circulate the primary water through the DHW plate heat exchanger.
  3. The burner will light automatically and the temperature of the domestic hot water is controlled by the temperature sensor.
  4. When the domestic hot water demand ceases the burner will extinguish and the diverter valve will remain in the domestic hot water mode, unless there is a demand for central heating.

IMPORTANT: When the selector switch is in the0’ (Off) position the electrical supply to the boiler is isolated. The boiler will not operate and the integral timer will require resetting once the selector switch is set to either Position (i) or Position (ii).

3.3 Frost Protection Mode

  1. The frost protection mode is integral to the appliance and functions only with the selector switch (see Section 2.1) in the domestic hot water and central heating position. If the system temperature falls below 5° C then the boiler will fire on its minimum setting until a flow temperature of 30° C is reached. Further protection can be incorporated by using a system frost thermostat.

3.4 Pump Protection

  1. With the selector switch (see Section 2.1) in either the central heating or central heating and domestic hot water position, the pump will automatically operate for 1 minute in every 24 hours to prevent sticking.

page 8


4.0 Technical Data

4.1 Platinum Combi 24 HE

 
Appliance Type  C13     C33
Appliance Category CAT I 2H
Heat Input CH (Net) 24.7 kW Max 7 kW Min
Heat Input CH (Gross) 27.4 kW Max 7.8 kW Min
Heat Output CH (Non-Condensing) 24 kW Max 6.8 kW Min
Heat Output CH (Condensing) 25.9 kW Max 7.4 kW Min
Heat Input DHW (Net) 24.7 kW Max
Heat Input DHW (Gross) 27.4 kW Max
Heat Output DHW 24 kW Max
Max Gas Rate (Natural Gas - G20) 2.61 m3/h (After 10 mins)
Inlet Pressure (Natural Gas - G20) 20 mbar
Injector (Natural Gas - G20) 7.5 mm
Electrical Supply
(Appliance must be connected to an earthed supply)
230V~ 50Hz
Power Consumption 155W
Electrical Protection IPX0D
External Fuse Rating 3A
Internal Fuse Rating F2L
NOx Class 5
Condensate Drain To accept 21.5 mm (3/4 in) plastic waste pipe
Flue Terminal Dimensions Diameter 100 mm
Projection 125 mm
Connections copper tails
Gas Supply 22 mm
Central Heating Flow 22 mm
Central Heating Return 22 mm
Cold Water Mains Inlet 15 mm
DHW Flow 15 mm
Pressure Relief Discharge 15 mm
Outercase Dimensions
Casing Height 780 mm
Overall Height Inc Flue Elbow 965 mm
Casing Width 450 mm
Casing Depth 345 mm
Clearances
Above Casing 200 mm Min
Below Casing 200 mm Min
Front 450 mm Min (For Servicing)
Front 5 mm Min (In Operation)
L.H. Side 5 mm Min
R.H. Side 5 mm Min (In Operation)
Weights
Packaged Boiler Carton 56.5 kg
Installation Lift Weight 45 kg
Central Heating Primary Circuit Pressures
Safety Discharge 3 bar
Max Operating 2.5 bar
Min Operating 0.5 bar
Recommended Operating Range 1-2 bar
DHW Circuit Pressures
Max Operating 8 bar
Min Operating 0.15 bar
Flow Rates
DHW Flow Rate @ 30°CRise 11.43 l/min
DHW Flow Rate @ 35°CRise 9.8 l/min
Min Working DHW Flow Rate 2 l/min
Pump
Available Head See graph below
Expansion Vessel (For Central Heating only. Integral with appliance)
Min Pre-charge Pressure 0.5 bar
Max Capacity of CH System 125 litre
Primary Water Content of Boiler (unpressurised) 2.5 litre
Temperatures
C.H. Flow Temp (adjustable) 25°C to 80°C max5°C
D.H.W. Flow Temp (adjustable) 35°C to 60°C max5°Cdependent upon flow rate

page 9


4.2 Platinum Combi 28 HE

 
Appliance Type  C13     C33
Appliance Category CAT I 2H
Heat Input CH (Net) 24.7 kW Max 9 kW Min
Heat Input CH (Gross) 27.4 kW Max 10 kW Min
Heat Output CH (Non-Condensing) 24 kW Max 8.7 kW Min
Heat Output CH (Condensing) 25.9 kW Max 9.5 kW Min
Heat Input DHW (Net) 28.9 kW Max
Heat Input DHW (Gross) 32.1 kW Max
Heat Output DHW 28 kW Max
Max Gas Rate (Natural Gas - G20) 3.1 m3/h (After 10 mins)
Inlet Pressure (Natural Gas - G20) 20 mbar
Injector (Natural Gas - G20) 7.5 mm
Electrical Supply
(Appliance must be connected to an earthed supply)
230V~ 50Hz
Power Consumption 155W
Electrical Protection IPX0D
External Fuse Rating 3A
Internal Fuse Rating F2L
NOx Class 5
Condensate Drain To accept 21.5 mm (3/ 4 in) plastic waste pipe
Flue Terminal Dimensions Diameter 100 mm
Projection 125 mm
Connections copper tails
Gas Supply 22 mm
Central Heating Flow 22 mm
Central Heating Return 22 mm
Cold Water Mains Inlet 15 mm
DHW Flow 15 mm
Pressure Relief Discharge 15 mm
Outercase Dimensions
Casing Height 780 mm
Overall Height Inc Flue Elbow 965 mm
Casing Width 450 mm
Casing Depth 345 mm
Clearances
Above Casing 200 mm Min
Below Casing 200 mm Min
Front 450 mm Min (For Servicing)
Front 5 mm Min (In Operation)
L.H. Side 5 mm Min
R.H. Side 5 mm Min (In Operation)
Weights
Packaged Boiler Carton 56.5 kg
Installation Lift Weight 45 kg
Central Heating Primary Circuit Pressures
Safety Discharge 3 bar
Max Operating 2.5 bar
Min Operating 0.5 bar
Recommended Operating Range 1-2 bar
DHW Circuit Pressures
Max Operating 8 bar
Min Operating 0.15 bar
Flow Rates
DHW Flow Rate @ 30°CRise 13.3 l/min
DHW Flow Rate @ 35°CRise 11.5 l/min
Min Working DHW Flow Rate 2 l/min
Pump
Available Head See graph below
Expansion Vessel (For Central Heating only. Integral with appliance)
Min Pre-charge Pressure 0.5 bar
Max Capacity of CH System 125 litre
Primary Water Content of Boiler (unpressurised) 2.5 litre
Temperatures
C.H. Flow Temp (adjustable) 25°C to 80°C max5°C
D.H.W. Flow Temp (adjustable) 35°C to 60°C max5°Cdependent upon flow rate

page 10


4.3 Platinum Combi 33 HE

 
Appliance Type  C13     C33
Appliance Category CAT I 2H
Heat Input CH (Net) 28.9 kW Max 9.7 kW Min
Heat Input CH (Gross) 32.1 kW Max 10.8 kW Min
Heat Output CH (Non-Condensing) 28 kW Max 9.4 kW Min
Heat Output CH (Condensing) 30.3 kW Max 10.2 kW Min
Heat Input DHW (Net) 34 kW Max
Heat Input DHW (Gross) 37.7 kW Max
Heat Output DHW 33 kW Max
Max Gas Rate (Natural Gas - G20) 3.6 m3/h (After 10 mins)
Inlet Pressure (Natural Gas - G20) 20 mbar
Injector (Natural Gas - G20) 12 mm
Electrical Supply
(Appliance must be connected to an earthed supply)
230V~ 50Hz
Power Consumption 160W
Electrical Protection IPX0D
External Fuse Rating 3A
Internal Fuse Rating F2L
NOx Class 5
Condensate Drain To accept 21.5 mm (3/ 4 in) plastic waste pipe
Flue Terminal Dimensions Diameter 100 mm
Projection 125 mm
Connections copper tails
Gas Supply 22 mm
Central Heating Flow 22 mm
Central Heating Return 22 mm
Cold Water Mains Inlet 15 mm
DHW Flow 15 mm
Pressure Relief Discharge 15 mm
Outercase Dimensions
Casing Height 780 mm
Overall Height Inc Flue Elbow 965 mm
Casing Width 450 mm
Casing Depth 345 mm
Clearances
Above Casing 200 mm Min
Below Casing 200 mm Min
Front 450 mm Min (For Servicing)
Front 5 mm Min (In Operation)
L.H. Side 5 mm Min
R.H. Side 5 mm Min (In Operation)
Weights
Packaged Boiler Carton 57.5 kg
Installation Lift Weight 46 kg
Central Heating Primary Circuit Pressures
Safety Discharge 3 bar
Max Operating 2.5 bar
Min Operating 0.5 bar
Recommended Operating Range 1-2 bar
DHW Circuit Pressures
Max Operating 8 bar
Min Operating 0.15 bar
Flow Rates
DHW Flow Rate @ 30°CRise 15.7 l/min
DHW Flow Rate @ 35°CRise 13.5 l/min
Min Working DHW Flow Rate 2 l/min
Pump
Available Head See graph below
Expansion Vessel (For Central Heating only. Integral with appliance)
Min Pre-charge Pressure 0.5 bar
Max Capacity of CH System 155 litre
Primary Water Content of Boiler (unpressurised) 2.8 litre
Temperatures
C.H. Flow Temp (adjustable) 25°C to 80°C max5°C
D.H.W. Flow Temp (adjustable) 35°C to 60°C max5°Cdependent upon flow rate

page 11


5.0 Dimensions and Fixings

page 12


6.0 System Details

6.1 Information

  1. The Baxi Platinum Combi HE Condensing Combination Boiler is aWater Byelaws Scheme - Approved Product’.
    To comply with the Water Byelaws your attention is drawn to the following installation requirements and notes (IRN).
         a) IRN 001 - See text of entry for installation requirements and notes.
         b) IRN 302 - Byelaw 14.
  2. Reference to the WRc publications, ‘Water fittings and materials directoryandWater supply byelaws guidegive full details of byelaws and the IRNs.

6.2 Central Heating Circuit

  1. The appliance is suitable for fully pumped SEALED SYSTEMS ONLY.

Treatment of Water Circulating Systems

Failure to flush and add inhibitor to the system will invalidate the appliance warranty.

6.3 Bypass

  1. The boiler is fitted with an automatic integral bypass.

6.4 System Control

  1. A 24 hour electro - mechanical timer is supplied fitted to the boiler.
  2. Further external controls (e.g. room thermostat) should be fitted to optimise the economical operation of the boiler.

page 13


6.5 System Filling and Pressurising

  1. A filling point connection on the central heating return pipework must be provided to facilitate initial filling and pressurising and also any subsequent water loss replacement/refilling.
  2. There are connection points on the mains cold water inlet and central heating return isolating taps (Fig. 5) to which the filling loop kit supplied can be assembled. If the boiler is to be installed in a location (e.g. loft space) the filling point must be accessible. The kit supplied can still be used for this, or if necessary a more suitable propriety kit.
  3. The filling method adopted must be in accordance with all relevant water supply regulations and use approved equipment.
  4. Your attention is drawn to:
    for GB: Guidance G24.2 and recommendation R24.2 of the Water Regulations Guide.
    for IE: the current edition of I.S. 813Domestic Gas Installations”.
  5. The sealed primary circuits may be filled or replenished by means of a temporary connection between the circuit and a supply pipe, provided aListeddouble check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use.

Fig. 4

 

6.6 Expansion Vessel (Central Heating only)

  1. The appliance expansion vessel is pre-charged to 0.5 bar. Therefore, the minimum cold fill pressure is 0.5 bar. The vessel is suitable for correct operation for system capacities up to 125 litres. For greater system capacities an additional expansion vessel must be fitted. For GB refer to BS 7074 Pt 1. For IE, the current edition of I.S. 813Domestic Gas Installations”.

6.7 Pressure Relief Valve (Fig. 6)

  1. The pressure relief valve is set at 3 bar, therefore all pipework, fittings, etc. should be suitable for pressures in excess of 3 bar and temperature in excess of 100°C.
  2. The pressure relief discharge pipe should be not less than 15mm dia, run continuously downward, and discharge outside the building, preferably over a drain. It should be routed in such a manner that no hazard occurs to occupants or causes damage to wiring or electrical components. The end of the pipe should terminate facing down and towards the wall.
  3. The discharge must not be above a window, entrance or other public access. Consideration must be given to the possibility that boiling water/steam could discharge from the pipe.

page 14


6.8 Domestic Hot Water Circuit (Fig. 7)

  1. All DHW circuits, connections, fittings, etc. should be fully in accordance with relevant standards and water supply regulations.
  2. Your attention is drawn to: for GB: Guidance G17 to G24 and recommendation R17 to R24 of the Water Regulations Guide. for IE: the current edition of I.S. 813Domestic Gas Installations”.
  3. A single check valve must be fitted as shown in Fig. 7 to prevent backflow to the supply pipe and to ensure the efficient operation of the expansion vessel which is required to accommodate the thermal expansion of the water.
  4. When the domestic water system includes any device which prevents water expanding back towards the supply (check valve, loose jumpered stopcock, water meter, water treatment device) then an expansion vessel must be fitted (eg. Zilmet 160ml, R1/2 15 bar). 
  5. If the hot water expansion is not provided for, then high pressures can develop which may result in damage to fittings and devices on the system.
  6. The boilers maximum working mains pressure is 8 bar, therefore all pipework, connections, fittings, etc. should be suitable for pressures in excess of 8 bar. A pressure reducing valve must be fitted for pressures in excess of 8 bar. The manufacturer of any outlet fittings, such as a shower valve, may require a lower maximum pressure. The pressure reduction must take account of all fittings connected to the DHW system.

6.9 Showers

  1. If a shower control is supplied from the appliance it should be of the thermostatic or pressure balanced type. Thermostatic type shower valves provide the best comfort and guard against water at too high a temperature. Existing controls may not be suitable - refer to the shower valve manufacturer.

6.10 Hard Water Areas

  1. If the area of the installation is recognised as a HARD WATER AREA then a suitable device should be fitted to treat the mains water supply to the boiler. Contact your Water Distribution Company for advice on suitable devices.

page 15


7.0 Site Requirements

7.1 Location

  1. The boiler may be fitted to any suitable wall with the flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard-see Section 7.3).
  2. If the boiler is sited in an unheated enclosure then it is recommended to leave the ON/OFF Selector Switch in the domestic hot water and central heating position to give frost protection.
  3. If the boiler is fitted in a room containing a bath or shower reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building Regulations. In IE reference should be made to the current edition of I.S. 813Domestic Gas Installationsand the current ETCI rules.
  4. If the boiler is to be fitted into a building of timber frame construction then reference must be made to the current edition of Institute of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).

7.2 Clearances (Fig. 8 & Fig9)

  1. A flat vertical area is required for the installation of the boiler.
  2. These dimensions include the necessary clearances around the boiler for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler.

page 16


7.3 Ventilation of Compartments

  1. Where the appliance is installed in a cupboard or compartment, no air vents are required.
  2. BS 5440: Part 2 refers to room sealed appliances installed in compartments. The appliance will run sufficiently cool without ventilation.

7.4 Gas Supply

  1. The gas installation should be in accordance with the relevant standards. In GB this is BS 6891. In IE this is the current edition of I.S. 813Domestic Gas Installations”.
  2. The connection to the appliance is a 22mm copper tail located at the rear of the gas service cock (Fig. 10).
  3. Ensure that the pipework from the meter to the appliance is of adequate size. Do not use pipes of a smaller diameter than the boiler gas connection (22mm).

7.5 Electrical Supply

  1. External wiring must be correctly earthed, polarised and in accordance with relevant regulations/rules. In GB this is the current I.E.E. Wiring Regulations. In IE reference should be made to the current edition of ETCI rules.
  2. The mains supply is 230V ~ 50Hz fused at 3A.

NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance.
Connection may be via a fused double-pole isolator with a contact separation of at least 3 mm in all poles and servicing the boiler and system controls only.

page 17


7.6 Condensate Drain

FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER
The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run.

  1. The condensate outlet will accept 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
  2. Ensure the discharge of condensate complies with any national or local regulations in force. BS 6798:2000 & Part H1 of the Building Regulations give further guidance.
  3. The discharge pipe should be run in a proprietary drain pipe material e.g. PVC, PVC-U, ABS, PVC-C or PP.
  4. Metal pipework is NOT suitable for use in condensate discharge systems.
  5. The pipe should be a minimum of 21.5mm diameter and must be supported using suitably spaced clips to prevent sagging.
  6. Any pipe fitted externally must not exceed 3 metres.
  7. Any condensate discharge pipework external to the building (or in an unheated part of it e.g. garage) must be insulated to protect against frost. It is also recommended that the pipe diameter is increased to 32mm.
  8. If the boiler is fitted in an unheated location the entire condensate discharge pipe should be treated as an external run.
  9. In all cases discharge pipe must be installed to aid disposal of the condensate. To reduce the risk of condensate being trapped, as few bends and fittings as possible should be used.
  10. When discharging condensate into a soil stack or waste pipe the effects of existing plumbing must be considered. If soil pipes or waste pipes are subjected to internal pressure fluctuations when WC's are flushed or sinks emptied then back-pressure may force water out of the boiler trap and cause appliance lockout.

Examples are shown of the following methods of termination:-

  1. to an internal soil & vent pipe
  2. via an internal discharge branch (e.g. sink waste)
  3. to a drain or gully
  4.  to a purpose made soakaway

page 18


7.7 Flue

NOTE: Due to the nature of the boiler a plume of water vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.

  1. The following guidelines indicate the general requirements for siting balanced flue terminals. For GB recommendations are given in BS 5440 Pt 1. For IE recommendations are given in the current edition of I.S. 813Domestic Gas Installations”.
  2. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
  3. If a terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be provided.

 

Terminal Position with Minimum Distance (Fig. 11)

(mm)

A

Directly below an openable window, air vent or any other ventilation opening.

300

B

Below gutter, drain/soil pipe.

25

C

Below eaves.

25

D

Below a balcony/car port roof.

25

E

From vertical drain pipes and soil pipes.

25

F

From internal or external corners.

25

G

Above adjacent ground or balcony level.

300

H

From a surface facing a terminal.

600

I

Facing a terminals.

1200

J

From opening (door/window) in carport into dwelling.

1200

K

Vertically from a terminal on the same wall.

1500

L

Horizontally from a terminal on the same wall.

300

M*

Above an opening, air brick, opening window etc.

300

N*

Horizontally to an opening, air brick, opening window etc.

300

* In addition, the terminal should be no nearer than 150mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame. See BS 5440 Pt. 1.

page 19


7.8 Flue Dimensions

The standard horizontal flue kit allows for flue lengths between 100mm and 685mm from elbow to terminal (Fig. 13).

The maximum permissible equivalent flue length is: 10 metres

7.9 Flue Trim

  1. The rubber flue trim supplied may be fitted to either the outside wall or on the inner wall of installation.

7.10 Terminal Guard (Fig. 14)

  1. When codes of practice dictate the use of terminal guards, they can be obtained from most Plumbersand BuildersMerchants.
  2. There must be a clearance of at least 50mm between any part of the terminal and the guard.
  3. When ordering a terminal guard, quote the appliance name and model number.
  4. The flue terminal guard should be positioned centrally over the terminal and fixed as illustrated.

page 20


7.11 Flue Options

  1. The Baxi Platinum Combi HE can be fitted with flue systems as illustrated.
  2. The standard flue is suitable only for horizontal termination applications.
  3. Maximum permissible equivalent flue lengths are:-
              Horizontal Concentric        10 metre
              Vertical Concentric            10 metres
              Vertical Twin Pipe             15 metres
  4. Any additionalin linebends in the flue system must be taken into consideration.
    Their equivalent lengths are:-
    Concentric Pipes:
              45° bend        0.5 metres
              93° bend        1.0 metres
     Twin Flue Pipe
              45° bend         0.25 metres
              91.5° bend      0.50 metres
    The elbow supplied with the boiler is not included in any equivalent length calculations
  5. The illustrations opposite show examples of permissible flue systems.
  6. Instructions for guidance and fitting are included in each kit, where appropriate.

NOTE: Flue length is measured from point A to B as shown.

page 21


8.0 Installation

8.1 Initial Preparation

The gas supply, gas type and pressure must be checked for suitability before connection (see Section 7.4).

  1. After considering the site requirements (see Section 7.0) position the fixing template on the wall ensuring it is level both horizontally and vertically.
  2. Mark the position of the two most suitable fixing slots for the wall plate and boiler lower fixing holes. It is preferable to use the horizontal fixing slots.
  3. Mark the position of the centre of the flue hole (rear exit). For side flue exit, mark as shown (Fig. 16).
  4. Note the shaded area on the template. Pipework may be routed upwards behind the boiler, providing it does not conflict with the shaded area.
  5. If required, mark the position of the gas and water pipes. Remove the template.
  6. Cut the hole for the flue (minimum diameter 116mm).
  7. Drill the wall as previously marked to accept the wall plugs supplied. Secure the wall plate using the fixing screws.
  8. Using a spirit level ensure that the plate is level before finally tightening the screws.
  9. Connect the gas and water pipes to the valves on the wall plate using the copper tails supplied. Ensure that the sealing washers are fitted between the connections.

8.2 Flushing

  1. Connect a tube to the central heating flow or return pipe (Fig. 17).
  2. Flush thoroughly (see System Details, Section 6.2).

8.3 Preparing The Boiler

  1. Remove all packaging.
  2. Stand the boiler on its base by using the rear lower edge as a pivot.

NOTE: A small amount of water may drain from the boiler in the upright position.

page 22


8.4 Fitting the Filling Loop

  1. The filling loop supplied with the boiler can be connected to the taps on the wall plate at this point.
  2. The filling loop is to be connected between the mains cold water inlet and central heating return isolation taps.
  3. The loop and valves must be connected as shown in the diagram (Fig. 17a).
  4. The two flanged copper elbows supplied are of different lengths (Fig. 17b). Use pipeAto connect to the cold inlet. PipeBshould be used to connect to the central heating return.
  5. Note the orientation of the flow direction arrows on the stop valve and double check valve.
  6. Ensure the brass flange nuts are on each pipe and connect the plain end of pipeAto the stop valve inlet and the plain end of pipeBto the outlet of the check valve using the nuts and washers supplied.
  7. Remove the end caps from the isolation taps and put to one side. Engage the brass flange nuts to the appropriate connections on the tap rail or pipework. Ensure that the fibre washers supplied are used on these joints.

To fill, test and flush if required (Fig. 17c)

  1. Take the blanking plugs from the kit, and using washers supplied with the boiler, connect them to the central heating flow and return taps, and the cold inlet tap. The system can now be filled by opening the cold inlet supply and stop valve.
  2. If desired a suitable gauge can be connected to one of the taps so that the system may be accurately pressurised.
  3. All joints, fittings and system components can now be examined for soundness at operating pressure.
  4. The system can be flushed by turning off the central heating tap and connecting a suitable fitting to the loose nut. From the fitting a hose pipe can be run to the nearest convenient drain. When the tap is reopened the system will flush.
  5. Remove the blanking plug(s), pressure gauge and flushing equipment from the appliance if used.
  6. Continue with the installation and commissioning.
  7. The filling loop must be disconnected and completely removed after the system is pressurised.
  8. Hand tighten the two previously removed end caps to the stop valve and double check valve.

page 23


8.5 Fitting The Boiler

  1. Remove the sealing caps from the boiler connections.
  2. Lift the boiler using the lower edges. Engage the slots at the top rear of the boiler on the wall plate (Fig. 18).
  3. Insert the sealing washers between the valves and pipes on the wall plate and the boiler connections. The rubber washers must be used on the gas connection.
  4. Tighten all the connections.

8.6 Fitting the Pressure Relief Discharge Pipe (Fig. 19)

  1. Remove the discharge pipe from the kit.
  2. Determine the routing of the discharge pipe in the vicinity of the boiler. Make up as much of the pipework as is practical, including the discharge pipe supplied.
  3. The pipework must be at least 15mm diameter and run continuously downwards to a discharge point outside the building. See section 6.7 for further details.
  4. Utilising one of the sealing washers, connect the discharge pipe to the adaptor and tighten the nut.
  5. Complete the discharge pipework and route it to the outside discharge point.

IMPORTANT: Make all soldered joints before connecting to the pressure relief valve.

8.7 Condensate Drain (see section 7.6)

  1. Connect the condensate drain to the trap outlet pipe.

Ensure the discharge of condensate complies with any national or local regulations in force (see British GasGuidance Notes for the Installation of Domestic Gas Condensing Boilers”.

  1. The connection will accept 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.

page 24


8.8 Fitting The Flue

HORIZONTAL FLUE

  1. The standard flue is suitable for lengths between 100mm minimum and 685mm maximum, as measured from the edge of the flue elbow outlet to the joint between the terminal and air duct (Fig. 20).
  2. Locate the flue elbow on the adaptor at the top of the boiler. Set the elbow to the required orientation (Fig. 21).

NOTE: The flue elbow is angled at 93 degrees to ensure a fall back to the boiler.

  1. Measure the distance from the outside wall face to the elbow. This dimension will be known asX’ (Fig. 22).
  2. To dimensionXadd 50mm. This dimension to be known asY’.

IMPORTANT: Check all dimensions before cutting.

page 25


8.8 Fitting the Flue (Cont)

  1. Mark dimensionYon the flue as shown (Fig. 23). Carefully cut the waste material from the flue, ensuring that the ducts are square and free from burrs.
  2. The inner flue duct support bracket may be in the waste portion of the flue. In this case retrieve the bracket before discarding the waste.
  3. Take the inner flue support bracket (if not already fitted) and engage it over the flue duct. This will centralise the flue and air ducts, and ease assembly (Fig. 24).
  4. Remove the flue elbow and insert the flue through the hole in the wall. Refit the elbow to the boiler adaptor, ensuring that it is pushed fully in.
  5. Draw the flue back through the wall and engage it in the elbow. It may be necessary to use soap solution or similar to ease assembly of the elbow adaptor and flue (Fig. 25).
  6. Ensure that the terminal is positioned with the slots to the bottom (Fig. 25a).

IMPORTANT: It is essential that the flue terminal is fitted as shown to ensure correct boiler operation and prevent water entering the flue.

  1. Make good between the wall and air duct outside the building.
  2. Fit the flue trim if required, and if necessary fit a terminal guard (see Section 7.9 & 7.10).

page 26


8.9 Making The Electrical Connections

To connect the mains input cable proceed as follows:-

  1. Slacken the facia panel securing screws and lift the outercase panel so that its securing tabs are clear of the facia. Remove the panel.
  2. Completely undo the screws securing the facia panel and hinge it down (Fig. 26).
  3. Remove the control box cover securing screws. Disengage the barbs on the control box from the cover. Remove the cover (Fig. 27).
  4. Slacken the cable clamp on the LH side of the boiler chassis (Fig. 28). Insert the cable through the clamp and route it to the terminal block.
  5. Slacken the screws in the terminal block, connect the input cable, and tighten the screws.
    NOTE: Both the Live and Neutral connections are fused.
  6. The boiler is fitted with an integral timer. If a room thermostat is to be connected it can be done at this point. Run the input cable from the thermostat through the second cable clamp on the boiler chassis. Refer to the instructions supplied with the control.
    IMPORTANT: The room thermostat MUST be suitable for 230V switching.
    NOTE: An external frost thermostat cannot be used with the integral timer.
  7. Remove the link between terminals 1 & 2. The 230V supply at terminal 1 can be connected to the thermostat. The switched output from the thermostat must be connected to terminal 2. (Fig. 29). If the room thermostat being used incorporates an anticipator it MUST be wired as shown in Fig. 29.
  8. Ensure that both mains input and, where fitted, external control input cables have sufficient slack to allow the control box to drop down. Tighten the cable clamp(s) on the boiler chassis.

8.10 Preliminary Electrical Checks

  1. Prior to commissioning the boiler preliminary electrical system checks should be carried out.
  2. These should be performed using a suitable meter, and include checks for Earth Continuity, Resistance to Earth, Short Circuit and Polarity.

page 27


9.0 Commissioning

9.1 Commissioning the Boiler

  1. Reference should be made to BS 5449 Section 5 when commissioning the boiler.
  2. Open the mains water supply to the boiler.
  3. Open all hot water taps to purge the DHW system.
  4. Ensure that the filling loop is connected and open, then open the heating flow and return valves on the boiler.
  5. Open the screw on the automatic air vent (Fig. 30).
  6. The system must be flushed in accordance with BS 7593 (see Section 6.2) and the flushing agent manufacturers instructions.
  7. Pressurise the system to 1.5 bar then close and disconnect the filling loop.
  8. Turn the gas supply on and purge according to in GB BS 6891 and in IE I.S. 813Domestic Gas Installations”.
  9. Test for gas soundness.
  10. Hinge the facia panel upwards and refit the case front panel. Tighten the securing screws.
  11. Turning either of the temperature control knobs will set the relevant temperature. When the knob is turned the display will alter and show the selected temperature. After a few seconds the display reverts to show the current boiler temperature (Fig. 32).

page 28


9.2 Setting the Timer

The Electro-Mechanical Timer allows the central heating system to be set every 15 minutes.

Using the three position switch the timer will allow either constant operation, timed operation or central heating off.

Move the switch button by sliding to the desired position.

Three position switch (Fig. 32a)

Constant (Top position): The heating will be on constantly irrespective of the position of the tappets. The heating will be controlled by the main thermostat on the appliance and/or any external controls.

Timed (Central position): The heating will operate according to the position of the tappets and be controlled as above.

Off (Bottom position): No central heating. Domestic hot water will operate on demand.

To set the time of day
Turn the timer outer bezel clockwise, to align the pointer with the correct time to the nearest 15 minutes ensuring that A.M./P.M. is considered. Do not at any time attempt to turn the bezel anti-clockwise.

To set the timed heating program
Decide which times of the day the central heating is required.

The heating will operate when the white tappets are set to the outer edge of the bezel.

To ensure the heating stays OFF set the required tappets inwards towards the centre of the bezel.

Each tappet represents 15 minutes.

For example:
If the heating is not required between 10 A.M. and 11 A.M. the four tappets anticlockwise from the 10 A.M. will be set inwards (Fig. 32b).

page 29


9.3 Checking

  1. The gas valve is factory set and the burner pressure cannot be measured as it is altered by suction of the fan and modulates as demand on the boiler alters. The gas supply pressure should be 20mb.
  2. If necessary the gas rate may be checked after running the boiler for 10 minutes with any other appliances and pilot lights turned off.
  3. Ensure that the integral timer and any external controls are calling for heat, and the selector switch is in the central heating and hot water position ( ). The current boiler temperature is shown on the display.
  4. To check the gas rate it is necessary to set the boiler toCalibration Mode’.
  5. Turn both temperature control knobs fully anticlockwise, then quickly turn the DHW temperature knob 1/ clockwise 4 twice and back fully anticlockwise (Fig. 33).
  6. The display will now alternate betweenSFand the current boiler temperature and both green LEDs will flash (Fig. 34 & Fig. 35).
  7. Turn CH temperature control knob fully clockwise. As the knob is turned the display will change from0to00’ (Fig. 36) indicating maximum rate, then revert toPalternating with the current boiler temperature (Fig. 37 & Fig. 38).
  8. A gas rate measurement may now be made. Approximate values are:-
             24 model        2.6 m3/h
             28 model        3.1 m3/h
             33 model        3.6 m3/h
  9. TheCalibration Functionis active for 20 minutes unless the maximum CH temperature is exceeded.
  10. The function can be disabled at any time by turning the DHW temperature knob.

page 30


10.0 Completion

10.1 Completion

  1. Instruct the user in the operation of the boiler and system including the integral timer, explaining the operational sequence.
  2. Set the central heating and hot water temperature control knobs to the requirements of the user.
  3. Carefully read and complete all sections of the Benchmark Commissioning Checklist at the rear of this publication that are relevant to the appliance and installation. These details will be required in the event of any warranty work. The publication must be handed to the user for safe keeping and each subsequent regular service visit recorded.
  4. For IE, it is necessary to complete aDeclaration of Conformityto indicate compliance with I.S. 813. An example of this is given in I.S. 813Domestic Gas Installations”. This is in addition to the Benchmark Commissioning Checklist.
  5. Hand over the Users Operating, Installation and Servicing Instructions giving advice on the necessity of regular servicing.

page 31


11.0 Servicing

11 .1 Annual Servicing

  1. For reasons of safety and economy, it is recommended that the boiler is serviced annually. Servicing must be performed by a competent person.

If a combustion analyser is available the CO2 can be checked and adjusted - see Section 13.0.

  1. After servicing, complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication.
  2. Ensure that the boiler is cool.
  3. Ensure that both the gas and electrical supplies to the boiler are isolated.
  4. Slacken the screws securing the facia panel. Lift the outercase panel so that its securing tabs are clear of the facia. Remove the panel, allowing the facia to hinge down (Fig. 40).
  5. Remove the screws securing the inner door panel. Lift the panel slightly to disengage it from the studs on top of the case (Fig. 41).
  6. Unscrew the sump from the bottom of the condensate trap assembly (Fig. 41a).
  7. Remove any deposits from the sump and trap. Clean as necessary and replace the sump.

page 32


11.1 Annual Servicing (Cont)

  1. Undo the nut on the gas inlet pipe to the venturi (Fig. 42) and pull the sensing pipe off the fan.
  2. Disconnect the electrode leads, noting their position, and the fan electrical plugs (Fig. 43).
  3. Undo the four nuts retaining the combustion box cover to the heat exchanger.
  4. Carefully draw the fan, collector and cover assembly forward, being careful to retain the injector in the venturi (Fig. 42 & Fig. 43).
  5. Clean any debris from the heat exchanger and check that the gaps between the tubes are clear.
  6. Inspect the burner, electrodes position and insulation, cleaning or replacing if necessary. Clean any dirt or dust from the air box.
  7. Reassemble in reverse order.

NOTE: The sensing pipe must be reconnected to the fan, not the venturi.

DHW Filter (Fig. 45)

  1. If the flow of domestic hot water is diminished, it may be necessary to clean the filter.
  2. Initially check the cold water inlet tap filter.
  3. Turn the tap off and draw off from a hot tap. Undo the blanking cap and remove the threaded bush (Fig. 44).
  4. Extract the filter and rinse thoroughly in clean water. Reassemble and check the flow. If required clean the restricter filter as described below.
  5. Pull off the hall effect sensor. Undo the restricter from the inlet/return manifold.
  6. Rinse the filter thoroughly in clean water and reassemble in reverse order.
  7. Turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 5 seconds to reset the boiler.
  8. Complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication and then hand it back to the user.

page 33


12.0 Changing Components

IMPORTANT: When changing components ensure that both the gas and electrical supplies to the boiler are isolated before any work is started. When the component has been changed turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 5 seconds to reset the boiler before recommissioning.

See Section 11.1Annual Servicingfor removal of case panel, door etc.

12.1 Igniter (Fig. 46)

  1. Disconnect the igniter feed plug and the electrode leads, noting their positions.
  2. Undo the screw securing the bracket to the boiler.
  3. Remove the igniter and transfer the bracket to the new component.
  4. Reassemble in reverse order.

12.2 Spark and Sensing Electrodes (Fig. 47)

  1. Disconnect the electrode leads, noting their positions.
  2. Remove the retaining screws securing each of the electrodes to the combustion box cover and remove the electrodes.
  3. Check the condition of the sealing gaskets and replace if necessary. Reassemble in reverse order.

page 34


12.3 Fan (Fig. 48)

  1. Undo the nut on the gas inlet pipe to the venturi (Fig. 49) and pull the sensing pipe off the fan.
  2. Disconnect the electrode leads, noting their position and disconnect the fan electrical plugs.
  3. Undo the screws securing the collector to the extension piece.
  4. Remove the collector and fan assembly, being careful to retain the injector in the venturi.
  5. Undo the screws securing the fan to the venturi and fit the new fan, replacing the seal if necessary.
  6. Examine the burner gasket and replace if necessary.
  7. Reassemble in reverse order, ensuring that the injector is in place and the sensing pipe is connected to the fan.

12.4 Venturi (Fig. 48)

  1. Remove the collector and fan assembly as described in section 12.3.
  2. Extract the injector from the venturi.
  3. Undo the screws securing the fan to the venturi and the venturi to the collector.

IMPORTANT: When fitting the new venturi, ensure the arrows on its base point into the collector (Fig. 50).

  1. Examine the seals and burner gasket, replace if necessary.
  2. Reassemble in reverse order, ensuring that the injector is in place.

12.5 Injector (Fig. 48)

  1. Remove the collector and fan assembly as described in section 12.3.
  2. Extract and replace the injector and reassemble in reverse order.

page 35


12.6 Burner (Fig. 51)

  1. Undo the screws securing the collector to the venturi and extension piece. Remove this extension piece from the cover (on 24 and 28 models).
  2. Withdraw the burner from the cover and replace with the new one.
  3. Examine the gasket, replacing if necessary.
  4. Reassemble in reverse order.

12.7 Insulation (Fig. 52)

  1. Remove the electrode leads, noting their positions. Also remove the electrodes as described in section 12.2.
  2. Undo the screws securing the collector to the venturi and the nuts holding the cover to the heat exchanger. Draw the collector and cover assembly away.
  3. Remove the cover insulation piece.
  4. Fit the new insulation carefully over the burner and align it with the slots for the electrodes.
  5. The rear insulation is retained by a screw and large washer, remove these and draw the insulation out of the heat exchanger.
  6. Examine the cover seal and replace if necessary.

page 36


12.8 Flue/Heat Exchanger Thermostat Sensor (Fig. 53)

  1. Ease the retaining tab on the sensor away and disconnect the electrical plug.
  2. Turn the sensor 90° anticlockwise to remove - it is a bayonet connection.
  3. Reassemble in reverse order.

12.9 Water Pressure Sensor (Fig. 54)

  1. Drain the primary circuit.
  2. Disconnect the two wires from the sensor.
  3. Undo the nut on the flow pipe securing and sealing the sensor.
  4. Remove the sensor, examine the sealing washer, replacing if necessary.
  5. Reassemble in reverse order. The component is not polarised - either wire will fit each terminal.

12.10 Central Heating Temperature Sensor (NTC) (Fig. 54)

  1. Ease the retaining tab on the sensor away and disconnect the electrical plug.
  2. Unscrew the sensor from its pocket and reassemble in reverse order. The plug will only fit one way.

12.11 Safety Thermostat (Fig. 54)

  1. Pull the plug off the thermostat.
  2. Remove the screws securing the thermostat to the mounting plate on the flow pipe.
  3. Reassemble in reverse order, ensuring that the plug is pushed fully on.

12.12 DHW Temperature Sensor (NTC) (Fig. 55)

  1. Turn off the mains cold water supply tap and draw off the residual domestic hot water.
  2. Ease the retaining tab on the sensor away and disconnect the electrical plug.
  3. Unscrew the sensor from the plate heat exchanger manifold. Examine the sealing washer, replacing if necessary.
  4. Reassemble in reverse order. The plug will only fit one way.

 

page 37


12.13 Pump - Head Only (Fig. 56)

  1. Drain the primary circuit and remove the socket head screws securing the pump head to the body and draw the head away.
  2. Undo the screw on the pump wiring cover and remove the cover. Using a suitable flat bladed screw driver press the cable securing levers downwards to release each wire after noting their position.
  3. A standard replacement Grundfos 15-60 head can now be fitted. Connect the pump wiring to the new head. The pump speed must be set to 3 (Fig. 57).
  4. Reassemble in reverse order.

12.14 Pump - Complete (Fig. 58)

  1. Drain the primary circuit.
  2. Undo the two screws securing the body to the pipe and manifold and draw the pump forwards.
  3. Undo the screw on the pump wiring cover and remove the cover. Using a suitable flat bladed screw driver press the cable securing levers downwards to release each wire after noting their position.
  4. Unscrew the automatic air vent from the pump body.
  5. Connect the wiring to the new pump. Examine theOring seals on the return pipe and manifold, replacing if necessary.
  6. Fit the air vent to the pump body and reassemble in reverse order.

12.15 Automatic Air Vent (Fig. 58)

  1. Drain the primary circuit and unscrew the automatic air vent from the pump body.
  2. Examine theOring seal, replacing if necessary, and fit it to the new automatic air vent.
  3. Reassemble in reverse order.

page 38


12.16 Pressure Gauge (Fig. 59 & Fig. 60)

  1. Drain the primary circuit and undo the nut on the pressure gauge capillary.
  2. Undo the screws securing the gauge retaining bracket.
  3. Remove the bracket and gauge assembly. Depress the barbs on the side of the gauge and remove the retaining bracket.
  4. Examine the sealing washer, replace if necessary.
  5. Reassemble in reverse order.

12.17 Hall Effect Sensor (Fig. 61)

  1. Ease the sensor upwards off the hydraulic inlet manifold assembly.
  2. Disconnect the electrical plug from the sensor.
  3. Connect the plug to the new sensor. Carefully fit the new sensor to the hydraulic assembly, ensuring it is fully down.

12.18 Pressure Relief Valve (Fig. 62)

  1. Drain the primary circuit.
  2. Disconnect the discharge pipe from the valve. Using a suitable hexagon key undo the grub screw sufficiently to release the valve.
  3. Note the orientation of the valve, rotate it and withdraw it from the manifold.
  4. Fit the new valve andOring seal and set to the previously noted orientation. Reassemble in reverse order.

page 39


12.19 Plate Heat Exchanger (Fig. 63)

  1. Drain the primary circuit and remove the gas valve as described in section 12.23.
  2. While supporting the heat exchanger undo the screws securing it to the brass manifolds.
  3. Withdraw the heat exchanger upwards, taking care not to damage any wires or controls.

Seals

  1. There are four rubber seals between the manifolds and heat exchanger which may need replacement.
  2. Ease the seals out of the manifold. Replace carefully, ensuring that when the seal is inserted into the manifold it is parallel and pushed fully in.
  3. When fitting the new heat exchanger note that the left hand location stud is offset towards the centre more than the right hand one.
  4. Reassemble in reverse order.

12.20 Diverter Valve - Motor Unit & Assembly (Fig. 64 & Fig. 65)

  1. To replace the motor unit, disconnect the multi-pin plug.
  2. Pull off the retaining clip and remove the motor unit.
  3. The motor unit can now be replaced, or the valve assembly removed.
  4. Drain the primary circuit and draw off any hot water once the isolating taps are closed.
  5. Remove the spring clip retaining the bypass pipe to the rear of the assembly and under the flow pipe nut at the left hand side.
  6. Undo the nuts on the tap rail under the boiler. Remove the screws securing the valve assembly to the boiler bottom panel and plate heat exchanger.
  7. Remove the valve assembly. Examine any seals or washers, replacing if necessary. Transfer the DHW NTC to the new valve and reassemble in reverse order.

page 40


12.21 P.C.B. (Fig. 66)

  1. Note the settings of the temperature control knobs, rotate them fully anticlockwise and carefully pull them off the drive pins.
  2. Completely undo the screws securing the control box cover and release the cover retaining barbs from their slots. Disengage the rear of the cover from the control box hinge pin (Fig. 66).
  3. Note the position of all plugs and wires on the P.C.B. and disconnect them.
  4. Undo the securing screws and remove the P.C.B. Transfer the control knob drive pins to the new P.C.B. and turn them fully anticlockwise.
  5. Reassemble in reverse order, ensuring that the temperature controllers are reset to their previous positions.

12.22 Selector Switch (Fig. 67)

  1. Note the setting of the selector switch knob and carefully pull it off the facia.
  2. Completely undo the screws securing the control box cover and release the cover retaining barbs from their slots. Disengage the rear of the cover from the control box hinge pin (Fig. 66).
  3. Note the position of the electrical connections and the orientation of the switch. Remove the electrical connections.
  4. Remove the screws securing the switch to the facia panel.
  5. Fit the new switch, ensuring that it is correctly positioned and reassemble in reverse order.

page 41


12.23 Gas Valve (Fig. 68)

  1. Turn the gas cock off and undo the nut on the gas feed elbow under the boiler.
  2. Remove the screws securing the inlet pipe flange to the boiler bottom panel.
  3. Pull off the earth lead and sensing pipe.
  4. Undo the nut on the venturi inlet pipe and slacken the nut on the venturi. Ease the pipe aside and remove the gas valve.
  5. Remove the outlet adaptor and inlet pipe and transfer them to the new valve. Examine theOring seals, replace if necessary.
  6. Reassemble in reverse order.

IMPORTANT: The CO2 must be checked and adjusted as detailed in Section 13.0 Combustion Check

12.24 Expansion Vessel (Fig. 69)

  1. Drain the primary circuit and undo the nut on the vessel connection pipe.
  2. Undo and remove the locknut and spring washer securing the vessel spigot to the boiler air box.
  3. Remove the bracket and vessel from the boiler.
  4. Locate the retaining bracket on the upper flange of the vessel and fit to the boiler.
  5. Reassemble in reverse order.

page 42


13.0 Combustion Check

13.1 Checking the CO2

  1. The combustion (CO2) may be checked using a suitably calibrated analyser after running the boiler for several minutes.
  2. To do this it is necessary to set the boiler toCalibration Mode’.
  3. Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
  4. Turn both temperature control knobs fully anticlockwise, then quickly turn the DHW temperature knob 1/ clockwise 4 twice and back fully anticlockwise (Fig. 70).
  5. The display will now alternate betweenSFand the current boiler temperature and both green LEDs will flash (Fig. 71 & Fig. 72).
  6. Turn the CH temperature knob fully clockwise. As the knob is turned the display will change, indicating the fan speed.
  7. The display will show00’, indicating maximum rate, then revert toPalternating with the current boiler temperature
    (Fig. 73, Fig. 74 & Fig. 75).
  8. Remove the plug from the flue adaptor test point. Insert the analyser probe and allow time for the reading to settle (Fig. 76). The CO2 should be 8.7% ± 0.2
  9. It is possible to alter the CO2 by adjustment of the gas valve. Remove the plastic cover from theMax Rateadjustment screw. At maximum rate theMax. Rateadjustment screw should be turned, using a suitable hexagon key, until the correct reading is obtained
    (Fig. 77).
  10. The CO2 must then be checked at minimum rate. Turn the CH temperature knob fully anticlockwise. As the knob is turned the display will change, indicating the fan speed. When the display reads0the boiler runs at minimum rate. The CO2 should be 8.4% ± 0.2.
  11. With the boiler on minimum, theMin. Rateadjustment screw must be altered, using a suitable hexagon key, after removing the cap
    (Fig. 77). If the CO2 is reset at either boiler rate it must be rechecked at the other rate and also adjusted if required.
  12. TheCalibration Functionis maintained for 20 minutes unless the maximum CH temperature is exceeded. The function can be disabled at any time by turning the DHW knob.

page 43


14.0 Electrical

14.1 Illustrated Wiring Diagram

page 44


15.0 Short Parts List

Short Parts List

Key
No.

Description

Manufacturers
Part No.

311 

Fan

5114684

426 

Motor 3way Valve

248733

315 

Igniter Electrode

5114702

316 

Sensing Electrode

5114703

422 

Gas Valve

5114734

624 

Hall Effect Sensor

5114767

306 

Burner 24/28
Burner 33

5114697
5114698

419 

Water Pressure Switch

5114748

400 

Plate Heat Exchanger

5114708

415 

Pump

248042

302 

Flue Thermostat

5114747

421 

NTC Sensor

5114725

420 

Overheat Thermostat

5114729

504 

Pressure Gauge

248090

503 

PCB 24
PCB 28
PCB 33

5116024
5115062
5114745

page 45


16.0 Fault Finding

16.1 Initial Fault Finding Checks

  1. Check that gas, water and electrical supplies are available at the boiler.
  2. Electrical supply = 230V ~ 50 Hz.
  3. CH water system pressurised to 0.5 bar minimum when the boiler is cold.
  4. The preferred minimum gas pressure is 20 mbar.
  5. Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter.

NOTE: These checks must be repeated after any servicing or fault finding.

  1. Ensure all external controls are calling for heat and check all external and internal fuses. Before any servicing or replacement of parts, ensure the gas and electrical supplies are isolated.

16.2 Error Codes

  1. If a fault occurs on the boiler an error code may be shown by the facia display.
  2. The codes are either two or three digit, preceded by the letter 'E'. For example, code E133 will be displayed by 'E1' alternating with '33'. E50 is shown as 'E' then '50'

E20, E28 & E50 indicate faulty components.

E110 shows overheat of the primary water and E130 overheat of the flue system.

E119 is displayed when the primary water pressure is less than 0.5 bar.

E133 indicates that the gas supply has been interrupted, ignition has failed or the flame has not been detected.

E125 is displayed in either of two situations:- 
i) If within 15 seconds of the burner lighting the boiler temperature has not changed by 1°.
ii) If within 10 minutes of the burner lighting the boiler temperature twice exceeds the selected temperature by 30°. In these instances the pump is probably inoperative.

  1. By turning the selector switch to the 'Reset' position for a minimum of 5 seconds when E110, E130 & E133 are displayed it is possible to relight the boiler.
  2. If this does not have any effect, or the codes are displayed regularly further investigation is required.

NOTE: When instructed to turn the selector to the reset position turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 5 seconds to reset the boiler.

Table Of Error Codes

E20

Central Heating NTC Fault

E50

Flue NTC Fault

E28

Hot Water NTC Fault

E110

Safety Thermostat Operated

E119

Water Pressure Switch Not Operated

E125

Pump Fault

E130

Flue NTC Operated

E133

Interruption Of Gas Supply or Flame Failure

E160

Fan or Fan Wiring Fault

page 46


Refer to Section 14.0Illustrated Wiring Diagramfor position of terminals and components
Central Heating - Follow operational sequence

page 47


Domestic Hot Water - Follow operational sequence

page 48


Fault Finding Solutions Sections

page 49


page 50


page 51


17.0 Notes

 

page 52


 

page 53


page 54


page 55


Baxi Heating UK Limited
Brownedge Road
Bamber Bridge
Preston
Lancashire
PR5 6UP

After Sales Service 08700 60 30 60
Technical Enquiries 08706 049 049

Website: www.baxi.co.uk

page 56